content loaded
TPS TK-TT2-065-3Y208-FL Image 1

TPS TK-TT2-065-3Y208-FL SERVICETRACK SURGE SUPPRESSION 65KVA

MFR Part #: TK-TT2-065-3Y208-FL
SKU #: 1133808
Brand: Total Protection Solutions™
UPC: 400008050203
Total Protection Solutions™ TransTrack®2 TK-TT2-065-3Y208-FL Surge Protection Device, 120/208 VAC, 47 to 63 Hz, 200 kA SCCR, 3 Phase
Pre-Wired Pigtail Conductors
Distribution Panels, Branch Panels and Critical Loads

Total Protection Solutions™ TransTrack®2 Surge Protection Device, 120/208 VAC Electrical Rating, 47 to 63 Hz Frequency, 4 Wires, 200 kA Short Circuit, 65 kA/Phase/32.5 kA/Mode Peak Surge Current, Modes of Protection: L-N/L-G/L-L/N-G, <1 ns Response, LED Indicator, 3 ph, Environmental Conditions: 5 to 95% Non-Condensing Relative Humidity, NEMA 4/IP56 Enclosure, Flanged Mounting, 6 in H x 6 in W x 4 in D Dimensions

Product Details

Total Protection Solutions™ TransTrack®2 Surge Protection Device, 120/208 VAC Electrical Rating, 47 to 63 Hz Frequency, 4 Wires, 200 kA Short Circuit, 65 kA/Phase/32.5 kA/Mode Peak Surge Current, Modes of Protection: L-N/L-G/L-L/N-G, <1 ns Response, LED Indicator, 3 ph, Environmental Conditions: 5 to 95% Non-Condensing Relative Humidity, NEMA 4/IP56 Enclosure, Flanged Mounting, 6 in H x 6 in W x 4 in D Dimensions

Attributes

Dimensions6 in H x 6 in W x 4 in D
Electrical Ratings120/208 VAC
Enclosure TypeNEMA 4/IP56
Environmental Conditions5 to 95% Non-Condensing Relative Humidity
Frequency Rating47 to 63 Hz
Indicator TypeLED
Modes of ProtectionL-N/L-G/L-L/N-G
Mounting TypeFlanged
Number of Wires4
Peak Surge Current65 kA/Phase/32.5 kA/Mode
Phase3
Response Time<1 ns
Short Circuit Current Rating200 kA

Features

  • Protects facilities and equipment against the harmful effects of lightning strikes and internally generated electrical transients
  • Individually fused MOV's provide superior protection and continuous operation
  • 200 kA IC short-circuit current rating allows direct bus connection without the need of an upstream over-current protection device
  • Includes pre-wired pigtail conductors to stream line installation
  • Low profile design has an optional flush-mount plate for most units for in-wall recessed panel application
  • UL 1283 EMI/RFI filter
  • Ultra compact footprint - makes installation flexible
  • Enhanced transient filter for better protection of electronic loads
  • 4-wire plus ground
  • 3000 impulses per mode repetitive surge current rating, based on actual test data (using ANSI/IEEE C62.41.1-2002 C3 combo wave)
  • Hybrid parallel design with individual fused MOV's and UL 1283 EMI/RFI filter
  • Parallel to electrical distribution system connection method
  • No upstream over-current protection device (breaker or fuse) required
  • Powder coated, impact-resistance steel enclosure
  • Pre-wired with 30 in of 10 AWG (5.26 sq-mm) conductor
  • 150 V for L-N/L-G/N-G, 300 V for L-L MCOV
  • 36 V at L-N mode/283 V at L-G mode/56 V at L-L mode/322 V at N-G mode, A1 ring wave/2 kV/67 A/180 deg phase angle
  • 590 V at L-N mode/597 V at L-G mode/980 V at L-L mode/590 V at N-G mode, B3/C1 impulse wave/6 kV/3 kA/90 deg phase angle
  • 970 V at L-N mode/1160 V at L-G mode/1490 V at L-L mode/1100 at N-G mode, C3 impulse wave/20 kV/10 kA/90 deg phase angle
  • 400/600 V at L-N mode/L-G mode/N-G mode, 800/1000 V at L-L mode UL 1449 voltage protection ratings