content loaded
SQUARE D QO260 Image 1

SQUARE D QO260 PUSH-IN 2 POLE 60 AMP BREAKER

MFR Part #: QO260
SKU #: 0715040
Brand: Square D™
UPC: 785901400561
Square D™ QO260 Standard 2-Pole Miniature Circuit Breaker, 120/240 VAC, 60 A, 10 kA Interrupt, 2 Poles, Thermal/Magnetic Trip
For providing overload and short circuit protection
CSA Certified | HACR Rated | RoHS Compliant | UL Listed

Square D™, QO260, 2-Pole Miniature Circuit Breaker, Standard, 120/240 VAC, 60 A, 50/60 Hz Frequency, 10 kA Interrupt, QO Frame, Thermal/Magnetic Trip, 2 Pole, 1 ph, Box Lug Connection, 8 to 2 AWG Wire, Plug-On Mounting, 40 deg C, 3 in H x 1.5 in W x 2.91 in D Dimensions

Standard thermal-magnetic QO and Homeline 15 and 20 A circuit breakers are listed to UL489 and provide overload and short circuit protection for conductors. The QO and Homeline thermal-magnetic circuit breakers are for general use in protecting branch circuit in residential and commercial applications. Use QO and Homeline 15 and 20 A arc fault circuit interrupter circuit breakers that have been listed to UL1699 in order to provide arc fault circuit protection for the entire branch circuit in accordance with the installation requirements in National Electrical Code section 210.12. Thermal-magnetic circuit breakers are not designed, listed, or intended to provide protection against low level hazardous arcing conditions in branch circuit wiring.

Product Details

Square D™, QO260, 2-Pole Miniature Circuit Breaker, Standard, 120/240 VAC, 60 A, 50/60 Hz Frequency, 10 kA Interrupt, QO Frame, Thermal/Magnetic Trip, 2 Pole, 1 ph, Box Lug Connection, 8 to 2 AWG Wire, Plug-On Mounting, 40 deg C, 3 in H x 1.5 in W x 2.91 in D Dimensions

Standard thermal-magnetic QO and Homeline 15 and 20 A circuit breakers are listed to UL489 and provide overload and short circuit protection for conductors. The QO and Homeline thermal-magnetic circuit breakers are for general use in protecting branch circuit in residential and commercial applications. Use QO and Homeline 15 and 20 A arc fault circuit interrupter circuit breakers that have been listed to UL1699 in order to provide arc fault circuit protection for the entire branch circuit in accordance with the installation requirements in National Electrical Code section 210.12. Thermal-magnetic circuit breakers are not designed, listed, or intended to provide protection against low level hazardous arcing conditions in branch circuit wiring.

Attributes

Amperage Rating60 A
Country Of OriginUS
Number of Poles2
Connection TypeBox Lug
Dimensions3 in H x 1.5 in W x 2.91 in D
FrameQO
Frequency Rating50/60 Hz
Interrupt Rating10 kA
Mounting TypePlug-On
Phase1
Temperature Rating40 deg C
Trip TypeThermal/Magnetic
TypeStandard
Voltage Rating120/240 VAC
Wire Size8 to 2 AWG

Features

  • QO and QOB circuit breakers have an overcenter, trip-free toggle mechanism with quick-make, quickbreak action and positive handle indication
  • The tripping mechanisms in two-and three-pole circuit breakers operate such that an overcurrent on any pole of the circuit breaker will cause all poles of the circuit breaker to open simultaneously
  • Plug-on QO circuit breakers are for use in QO load centers, NQ and NQOD panelboards, OEM mounting bases, and Speed D™ switchboard distribution panels
  • 8 - 2 AWG copper/aluminum
  • Common trip
  • Standard