content loaded
HONEYWELL V8944B1027 Image 1

HONEYWELL V8944B1027 1-1/4IN TWO-STAGE PRESSURE REG VALVE

MFR Part #: V8944B1027
SKU #: 1039026
Brand: Honeywell
UPC: 085267164337
Honeywell V8944B1027 Diaphragm Gas Valve, 1-1/4 in, NPT, 0.5 psi, Aluminum
For atmospheric boilers, commercial water heaters, duct furnaces, makeup air and rooftop heaters
UL File No. MH1639 Guide No. YIOZ | CSA 158158-1042930 Guide No. 3371-03 | 83 (Z21.21 | Z21.78) Certified

Honeywell Diaphragm Gas Valve, 1-1/4 in Nominal, NPT Connection, 0.5 psi, Aluminum, 2 Stages, 1/4 in Spade Quick-Connect Terminal, 30 in Lead Wire Electrical Connection, 0.516 A, 24 VAC, 60 Hz, 480 to 1600 cfh Nominal Capacity, 12.4 VA Power Consumption, Natural Gas Fuel, Horizontal Mounting, -40 to 150 deg F, 6-9/16 in H x 6 in W x 6 in D

V4944B,L,N/8944B,C,L,N are two stage pressure regulating gas valve. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters.

Product Details

Honeywell Diaphragm Gas Valve, 1-1/4 in Nominal, NPT Connection, 0.5 psi, Aluminum, 2 Stages, 1/4 in Spade Quick-Connect Terminal, 30 in Lead Wire Electrical Connection, 0.516 A, 24 VAC, 60 Hz, 480 to 1600 cfh Nominal Capacity, 12.4 VA Power Consumption, Natural Gas Fuel, Horizontal Mounting, -40 to 150 deg F, 6-9/16 in H x 6 in W x 6 in D

V4944B,L,N/8944B,C,L,N are two stage pressure regulating gas valve. These valves are used on boilers, unit heaters, duct furnaces, makeup air and rooftop heaters.

Attributes

Amperage Rating: .516 A
Connection Type: NPT
Dimensions: 6-9/16 in H x 6 in W x 6 in D
Electrical Connection: 1/4 in Spade Quick-Connect Terminal, 30 in Lead Wire
Frequency Rating: 60 Hz
Fuel Type: Natural Gas
Material: Aluminum
Mounting Type: Horizontal
Nominal Capacity: 480 to 1600 cfh
Nominal Size: 1-1/4 in
Number of Stages: 2
Power Consumption: 12.4 VA
Pressure Rating: .5 psi
Temperature Rating: -40 to 150 deg F
Voltage Rating: 24 VAC

Features

  • V8944 are used with 24 VAC dual stage thermostats or controllers
  • Valve closes on power failure and recommended for final shut-off service
  • Cover for electrical conduit connection
  • Two 5/16-24 UNF bleed tapping
  • 3 to 25 s valve opening and 2 s maximum valve closing time
  • Adjustable range pressure regulator set point
  • Straight through configuration