content loaded
CARLO GAVAZZI DIA 01 C B23 5A Image 1

CARLO GAVAZZI DIA01CB235A MONITORING RELAY 1PHS AC/DC O/C

MFR Part #: DIA 01 C B23 5A
SKU #: 1062155
Brand: Carlo Gavazzi
UPC: 8030960000000
Carlo Gavazzi DIA 01 C B23 5A DIA01 1-Phase Monitoring Relay, 115/230 VAC, 5 A, SPDT Contact

Carlo Gavazzi 1-Phase Monitoring Relay, Series: DIA01, 115/230 VAC, 5 A, SPDT, DIN Rail Mount, Y1/Y2 Terminal, LED, <100 to 300 ms Response, IP20

DIA01 and PIA01 are precise AC/DC over current monitoring relays. Direct measuring or through current transformer. Owing to the built-in latch function, the ON-position ofthe relay output can be maintained. The red LED indicates the relay status. Through the built-in shunt it is possible to monitor loads up to 5 A AC/DC.

Product Details

Carlo Gavazzi 1-Phase Monitoring Relay, Series: DIA01, 115/230 VAC, 5 A, SPDT, DIN Rail Mount, Y1/Y2 Terminal, LED, <100 to 300 ms Response, IP20

DIA01 and PIA01 are precise AC/DC over current monitoring relays. Direct measuring or through current transformer. Owing to the built-in latch function, the ON-position ofthe relay output can be maintained. The red LED indicates the relay status. Through the built-in shunt it is possible to monitor loads up to 5 A AC/DC.

Attributes

Amperage Rating5 A
Contact ConfigurationSPDT
Display TypeLED
Enclosure TypeIP20
Mounting TypeDIN Rail
Response Time<100 to 300 ms
SeriesDIA01
Terminal TypeY1/Y2
Voltage Rating115/230 VAC

Features

  • AC/DC over current monitoring relay
  • Current measured through internal shunt
  • Measuring ranges from 0.5 to 5 A AC/DC
  • Adjustable current limit on relative scale
  • Adjustable hysteresis
  • Programmable latching at set level
  • Output 8 A SPDT relay normally de-energized
  • For mounting on DIN-rail in accordance with DIN/EN 50 022 (DIA01) or plug-in module (PIA01)
  • 22.5 mm euronorm housing (DIA01) or 36 mm plug-in module (PIA01)
  • LED indication for relay and power supply ON
  • Galvanically separated power supply
  • 0.05 Ohm internal resistance
  • 250 VAC rated insulation voltage
  • 30 x 10^6 operations mechanical life
  • 10^5 operations electrical life
  • 7200 operations/h operating frequency
  • 2 kVAC (rms) dielectric voltage
  • 4 kV rated impulse withstand voltage
  • +/- 1000 ppm/deg C temperature drift
  • +/- 0.5% on full-scale repeatability