APPLETON EYM50AL 1/2 ALMAG 35 SEALING FITTING

MFR Part #: EYM50-AL
SKU #: 1243496
Brand: Appleton®
UPC: 78138160009
Appleton® UNILETS® EYM50-AL Dust-Ignitionproof Explosionproof Raintight Conduit Sealing Fitting With Removable Nipple, 1/2 in, For Use With IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated
Limited
For prevent passage of gases, vapors or flames from one portion of conduit system to another
UL 886 | UL 1203 File No. E10444 | CSA C22.2 No. 30 | CSA 065181, Class I, Groups A, B, C, D, Class II, Groups E, F, G, Class III

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 4.72 in L x 1.19 in W

Product Details

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 4.72 in L x 1.19 in W

Attributes

Country Of Origin: Mexico
Size: 1/2 in
Dimensions: 4.72 in L x 1.19 in W
Finish: Epoxy Powder Coated
Material: Almag 35 Aluminum
Series: EY Series
Suitable For Use With: IMC/Threaded Rigid Metallic Conduit
Type: Dust-Ignitionproof Explosionproof Raintight

Features

  • Smooth, rounded integral bushing in each hub to protect conductor insulation
  • Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • Restrict any explosion to the sealed off enclosure
  • Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
  • Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
  • 25% fill vertical and horizontal conduit sealing fittings for close turning radius